Back
back to all categoriesUPS Modular Tower THOR 31 6-30 kVA
For the highest demands on flexibility and reliability, EFFEKTA® recommends the new THOR 31 UPS system with 3-phase input and 1-phase output.
The outstanding efficiency of up to 99% in ECO mode makes this system one of the most efficient UPS systems on the market.
The modular design with 6 kVA / kW modules allows to set up a high availability UPS system up to 30 kW with a total of 5 modules. With their help, an n+x redundancy can be set up. Furthermore, up to 4 systems can be connected in parallel.
Open in the catalogueDownloads
UPS THOR 31_6-30 kVA - data sheet
1 file(s) 166.10 KB
UPSTHOR 31_6-30 kVA - Manual
1 file(s) 2.83 MB
Characteristics
- UPS classification VFI-SS-111 according to IEC 62040-3
- Online double conversion UPS with sine wave output switchable to high efficiency mode
- Battery remaining time on LCD display
- Extraordinarily compact design
- Service-friendly battery replacement
- UPS software for all common OS
- Incl. 2 expansion slots
- Integrated remote emergency stop contact (REPO)
- 24 months warranty
Special feature
- Unbeatable price advantage in this power class
- Outstanding power factor of 1.0
- Outstanding efficiency of up to 94.5% in normal operation
- Mains feedback THDi <2.5%
- Automatic battery test adjustable via display
- Low noise due to intelligent fan control
- Dry-in/dry-out interface as standard
- Parallel redundant operation possible
- Multilingual 7“-large LC-color touch display
Specifications
Model THOR Modular 31 | 6 – 30 kVA | |
---|---|---|
Power | Nominal power in VA/W | 6000 – 30000 |
Power per module | 6 kVA / 6 kW | |
Bridging time | UPS system THOR Modular 31 | Configurable according to number of modules and battery capacity |
Technology | Online continuous converter | n+x technology scalable / VFI-SS-111 according to IEC 62040-3 |
Phases | Input/Output | 1-phase/1-phase or 3-phase/1-phase |
Input | Nominal voltage configurable | 380/400/415 VAC or 220/230/240 VAC |
Input voltage range | 208~478 VAC or 120~276 VAC | |
Input frequency range | 40-70 Hz (automatic detection) | |
Mains feedback THDi | ≤3% (100% non-linear load). | |
Output | Output voltage | 220/230/240 VAC |
Power factor | 1,0 | |
Voltage regulation | ±1 % | |
Frequency range | Mains operation: ±1%, ±2%, ±4%, ±5%, ±10% of rated frequency (optional). Battery operation: 50 Hz / 60 Hz ± 0.2 Hz | |
Changeover time | 0 ms | |
Overload normal operation | ≤110%: for 60 min, ≤125%: for 10 min, ≤150%: for 1 min, ≥150% immediate switchover to bypass. | |
Overload battery operation | ≤110%: for 10 min, ≤125%: for 1 min, ≤150%: for 1 sec, ≥150% immediate switch-off of the UPS. | |
Voltage mode | Sine wave | |
Crest factor | 3:1 | |
THD | ≤2% with linear load ≤5% with non-linear load | |
Efficiency | Normal operation | max. 94 % |
ECO operation | max. 98 % | |
Battery | Type | Maintenance-free lead-fleece accumulators |
Service life expectancy | 5 years (optional 10 years) | |
DC rated voltage | 192-240 VDC adjustable, standard 240VDC | |
Maximum charging current | max. 12A per power module / max. 60 A UPS system | |
Communication | Interfaces | RS232, 2xRS485, switching contacts, REPO |
Expansion slot | 2 x for relay or SNMP card | |
Display | LCD display and LED indicators | |
Dimensions / Weight | UPS dimensions (HxWxD in mm) | 1400 x 600 x 840 |
Weight UPS without modules in kg | 150 | |
Weight UPS power module in kg | 25 | |
Dimensions battery cabinet (HxWxD in mm) | 1200 x 600 x 780 | |
Weight battery cabinet in kg | depending on battery configuration | |
Protection class | IP20 | |
Connections | Input | Fixed connection on terminals |
Output | Fixed connection on terminals | |
Environmental conditions | Temperature | 0°C – 40°C, 20°C recommended |
Humidity | 0-95% RH (non-condensing) | |
Protection / Standards | Safety | EN 62040-1 |
EMC | EN 62040-2 class C3 | |
Approvals | CE |
Options for advanced communication and highest availability:
- SNMP/web or relay card for monitoring in network environments.
- Additional battery modules to increase backup time to several hours
- External manual bypass for scheduled UPS maintenance or UPS replacement without shutdown
- Special designs available for industrial applications (connectors / special enclosures, etc.)