THOR II TB20 10-60 kVA




With the THOR II TB20, EFFEKTA® offers a compact, modular online double-conversion converter with 3-phase input and output in 3-level inverter technology.

Integrated, space-saving, modular battery expansion modules to increase the backup time, even retroactively.

The control elements, interfaces, battery packs and power modules are accessible from the front for easy commissioning, operation and maintenance.

Downloads

Characteristics

  • UPS classifi cation VFI-SS-111 according to IEC 62040-3
  • VFI sine wave output can be switched to ECO High Effi ciency mode
  • UPS software for all common OS
  • Incl. RS232 / USB and expansion slot
  • Integrated Emergency Power Off (EPO)

Special feature

  • Excellent power factor of 1.0
  • Intelligent battery management with configurable charging mode
  • N + X parallel redundant operation of up to 6 systems
  • Redundant parallel control unit
  • Power supply modules and fans redundant
  • Outstanding efficiency of over 95.5% in normal operation, over 99% in eco mode
  • Large 7 “multi-language touchscreen LCD panel

Specifications

THOR II T20 10-30 kVA/kW 20-60 kVA/kW
Power Nominal power in kVA/kW 10-30 kVA/kW 20-60 kVA/kW
Power per module 10 kVA/kW 20 kVA/kW
Number of modules max. 3
Backup time On request / depending on the battery configuration
Technology n + x technology scalable / VFI-SS-111 according to IEC 62040-3
Phases Input / Output 3-phase / 3-phase
Input Configurable nominal voltage 380 / 400 / 415 VAC
Input voltage range 138 ~ 485 VAC
Input frequency range 40Hz – 70Hz
Mains feedbacks THDI ≤3 % (100% nichtlineare Last)
Output Output voltage 380 / 400 / 415 VAC
Voltage regulation ±1 %
Frequency range Normal mode ±1 % / ±2 % / ±4 % / ±5 % / ±10 % of the nominal frequency (optional)
Frequency range Battery mode 50/60 Hz ± 0,2 %
Transfer time None
Overload For mains operation: 105 % < load ≤ 110 %: Switching to bypass after 60 min.
110 % < load ≤ 125 %: Switchover to bypass after 10 min
125 % < load ≤ 150 %: Switchover to bypass after 1 min
125 % < load ≤ 150 %: Switchover to bypass after 1 min
THD > 150 %: immediate switch-off
Voltage form Sine wave
Effi ciency Normal-Mode max. 95.5 %
Batteries Type Maintenance free lead-acid battery
Service life expectancy 5 / 10 Jahre
DC nominal voltage ±240 VDC
Batteries used Max. 5 battery slots with max. 40 x 12V, 9.5 AH batteries per battery slot
Maximum charging current 18 A power module (charging current is set according to the battery bank equipment)
per UPS cabinet 54 A per UPS cabinet
Time to recharge depending on battery capacity
Communication Interfaces CAN, RS232, RS485, LBS, parallel, relay card, SNMP card (optional)
Display multilingual LC display
Dimensions / weight UPS dimensions (H x W x D in mm) 2000 x 600 x 1000
UPS modules (H x W x D in mm) 86 (2U) x 440 x 620
Weight UPS in kg (without batt.) approx. 363 kg
UPS modules 19 kg / 21 kg
Weight battery bank (with batt.) approx. 120 kg
Protection class IP20
Connections Input | Output fixed connection on terminals | fixed connection on terminals
Environmental conditions Temperature [0 – 40 °C], Recommended: + 15 °C…+ 25 °C
Humidity 0 ~ 95 % (non-condensing)
Operating noise < 61 dB
Protection / standards Safety | EMC | Service EN 62040-1 | EN 62040-2 | EN 62040-3
Certification CE