Back

3-phase modular UPS THOR II TB20 10-60 kVA


Integrated Battery Modules

With the THOR II TB20, EFFEKTA® offers a compact, modular online double-conversion converter with 3-phase input and output in 3-level inverter technology.

Integrated, space-saving, modular battery expansion modules to increase the backup time, even retroactively.

The control elements, interfaces, battery packs and power modules are accessible from the front for easy commissioning, operation and maintenance.

Open in the catalogue

Characteristics

  • UPS classifi cation VFI-SS-111 according to IEC 62040-3
  • VFI sine wave output can be switched to ECO High Effi ciency mode
  • UPS software for all common OS
  • Incl. RS232 / USB and expansion slot
  • Integrated Emergency Power Off (EPO)
  • 24 months warranty

Special feature

  • Excellent power factor of 1.0
  • Intelligent battery management with configurable charging mode
  • N + X parallel redundant operation of up to 6 systems
  • Redundant parallel control unit
  • Power supply modules and fans redundant
  • Outstanding efficiency of over 95.5% in normal operation, over 99% in eco mode
  • Large 7 “multi-language touchscreen LCD panel

Specifications

THOR II T2010-30 kVA/kW20-60 kVA/kW
PowerNominal power in kVA/kW10-30 kVA/kW20-60 kVA/kW
Power per module10 kVA/kW20 kVA/kW
Number of modules max.3
Backup timeOn request / depending on the battery configuration
Technologyn + x technology scalable / VFI-SS-111 according to IEC 62040-3
PhasesInput / Output3-phase / 3-phase
InputConfigurable nominal voltage380 / 400 / 415 VAC
Input voltage range138 ~ 485 VAC
Input frequency range40Hz – 70Hz
Mains feedbacksTHDI≤3 % (100% nichtlineare Last)
OutputOutput voltage380 / 400 / 415 VAC
Voltage regulation±1 %
Frequency range Normal mode±1 % / ±2 % / ±4 % / ±5 % / ±10 % of the nominal frequency (optional)
Frequency range Battery mode50/60 Hz ± 0,2 %
Transfer timeNone
OverloadFor mains operation: 105 % < load ≤ 110 %: Switching to bypass after 60 min.
110 % < load ≤ 125 %: Switchover to bypass after 10 min
125 % < load ≤ 150 %: Switchover to bypass after 1 min
125 % < load ≤ 150 %: Switchover to bypass after 1 min
THD> 150 %: immediate switch-off
Voltage formSine wave
Effi ciencyNormal-Modemax. 95.5 %
BatteriesTypeMaintenance free lead-acid battery
Service life expectancy5 / 10 Jahre
DC nominal voltage±240 VDC
Batteries usedMax. 5 battery slots with max. 40 x 12V, 9.5 AH batteries per battery slot
Maximum charging current18 A power module (charging current is set according to the battery bank equipment)
per UPS cabinet54 A per UPS cabinet
Time to rechargedepending on battery capacity
CommunicationInterfacesCAN, RS232, RS485, LBS, parallel, relay card, SNMP card (optional)
Displaymultilingual LC display
Dimensions / weightUPS dimensions (H x W x D in mm)2000 x 600 x 1000
UPS modules (H x W x D in mm)86 (2U) x 440 x 620
Weight UPS in kg (without batt.)approx. 363 kg
UPS modules19 kg / 21 kg
Weight battery bank (with batt.)approx. 120 kg
Protection classIP20
ConnectionsInput | Outputfixed connection on terminals | fixed connection on terminals
Environmental conditionsTemperature[0 – 40 °C], Recommended: + 15 °C…+ 25 °C
Humidity0 ~ 95 % (non-condensing)
Operating noise< 61 dB
Protection / standardsSafety | EMC | ServiceEN 62040-1 | EN 62040-2 | EN 62040-3
CertificationCE

Options for extended communication and highest availability:

  • SNMP/web for monitoring in network environments
  • Additional batteries to increase backup time to several hours
  • External manual bypass
back to all categories

Newsletter