Back

ADIRA T 6-10 kVA


The ADIRA T is currently the most compact online double conversion UPS system and can be used in the smallest space. It can be extended extremely flexibly in the autonomy time by external battery packs. The current consumption is almost perfectly sinusoidal. Furthermore, the ADIRA T offers a power factor of 1.0. With an effi ciency of up to 95% in normal operation, it is one of the most effective and economical UPS systems on the market and thus ideally suited to save cash.

Open in the catalogue

Downloads

Characteristics

  • UPS classification VFI-SS-111 according to IEC 62040-3
  • VFI sine wave output can be switched to High Efficiency mode
  • Battery remaining indicator on LCD display
  • Extremely compact design
  • UPS software for all common OS
  • Incl. RS232 / USB and expansion slot
  • Integrated Emergency Power Off (EPO)
  • 24 months warranty

Special feature

  • Excellent power factor of 1.0
  • Superior efficiency of up to 95% in normal operation
  • Battery number can be set to 16 up to 20 pc. per battery string
  • Low noise thanks to intelligent fan control
  • Larger 12A charger for higher charging currents (XL)
  • Dry-In / Dry-Out interface as standard
  • Parallel redundant operation possible
  • Multi-language LC display. English, German or Spanish as menu language selectable

Specifications

ADIRA-T600010000
PowerPower in VA6000/600010000/10000
Autonomy time 100/50%
load (cos. phi 0.7)
With internal batteries in minutes12/256/13
Higher autonomy timesAs XL-model on request
TechnologyOnline double conversionVFI-SS-111 in accordance with IEC 62040-3
PhaseInput / Output1- phase / 1-phase
Input voltage range160-276VAC
Input frequency range50/60Hz (Auto-Sensing)
OutputOutput voltage220/230/240 VAC
Voltage regulation±1%
Frequency range50Hz / 60Hz ± 1Hz
Transfer timeNone
Overload Capability (Line Mode)< 125% for 10min., < 150% for 30sec.
Voltage formsine wave
EfficiencyNormal mode / ECO modemax. 95% / max. 98%
BatteryNominal DC-voltage240VDC
Charging current (max)4A Standard / 12A XL-version
Recharging timeca. 3h to 90% capacity depending on the equipment
InterfaceRS232, USB, switch contacts, EPO, parallel port
CommunicationSlot for further communication cardsOptional relays- or SNMP-card
DisplayLCD Display and LED
Dimensions / WeightDimensions UPS (HxWxD in mm)589 x 225 x 600 (XL-version: 348 x 225 x 600)
Dimensions of battery extension
(H x W x D in mm) optional
589 x 225 x 490
Weight UPS (without batt. / XL)14 kg16 kg
Weight UPS (Standard)68 kg70 kg
Weight battery pack66 / 116 kg
ProtectionIP20
TerminalsInputFixed connection on terminals
OutputFixed connection on terminals
Environmental conditionsTemperature0°C – 40°C, 20°C recommended
Humidity0-90 % RH @ 0- 40°C (non condensing)
Acoustic Noise40 – 55dB(A)@1m45 – 60dB(A)@1m
Safety / EnclosureSafetyEN 62040-1
EMCEN 62040-2 class C3
CertificationsCE