ADIRA RT 6-10 kVA




The ADIRA RT is currently the most compact online double conversion UPS system and can be used in the smallest space. It can be extended extremely flexibly in the autonomy time by external battery packs. With its Racktower design, it can also be used in 19"-cabinets as a plug-in device. The current consumption is almost perfectly sinusoidal. Furthermore, the ADIRA RT offers a power factor of 1.0. With an effi ciency of up to 95% in normal operation, it is one of the most effective and economical UPS systems on the market and thus ideally suited to save cash.

Downloads

Characteristics

  • UPS classification VFI-SS-111 according to IEC 62040-3
  • VFI sine wave output can be switched to High Efficiency mode
  • Battery remaining indicator on LCD display
  • Extremely compact design
  • UPS software for all common OS
  • Incl. RS232 / USB and expansion slot
  • Integrated Emergency Power Off (EPO)
  • Rack Tower Design: Can be used as tower or 19″
  • 24 months warranty

Special feature

  • Excellent power factor of 1.0
  • Superior efficiency of up to 95% in normal operation and up to 98% in ECO-mode
  • Battery number can be set to 16 up to 20 pc. per battery string
  • Low noise thanks to intelligent fan control
  • Larger 12A charger for higher charging currents (XL)
  • Dry-In / Dry-Out interface as standard
  • Parallel redundant operation possible
  • Multi-language LC display. English, German or Spanish as menu language selectable

Specifications

ADIRA-RT 6000 10000
Power Power in VA 6000/6000 10000/10000
Autonomy time 100/50%
load (cos. phi 0.7)
With internal batteries in minutes 12/25 6/13
Higher autonomy times As XL-model on request
Technology Online double conversion VFI-SS-111 in accordance with IEC 62040-3
Phase Input / Output 1- phase / 1-phase
Input Nominal voltage configurable 220/230/240VAC
Input voltage range 160-276VAC
Input frequency range 50/60Hz (Auto-Sensing)
Output Output voltage 220/230/240 VAC
Voltage regulation ±1%
Frequency range 50Hz / 60Hz ± 1Hz
Transfer time None
Overload Capability (Line Mode) < 125% for 10min., < 150% for 30sec.
Voltage form sine wave
Efficiency Normal mode / ECO mode max. 95% / max. 98%
Battery Type Maintenance free lead-acid battery
Life time 5 years, optional 10 years
Nominal DC-voltage 240VDC
Charging current (max) 4A Standard / 12A XL-version
Recharging time ca. 3h to 90% capacity depending on the equipment
Communication Interface RS232, USB, switch contacts, EPO, parallel port
Slot for further communication cards Optional relays- or SNMP-card
Display LCD Display and LED
Dimensions / Weight Dimensions UPS (HxWxD in mm) 2U x 438 x 685
Dimensions of battery extension
(H x W x D in mm) optional
3U x 438 x 625
Weight UPS (without batt.) 14 kg 16 kg
Weight battery pack 62 kg
Protection IP20 (optionally higher degrees of protection possible)
Terminals Input Fixed connection on terminals
Output Fixed connection on terminals
Environmental conditions Temperature 0°C – 40°C, 20°C recommended
Humidity 0-90 % RH @ 0- 40°C (non condensing)
Acoustic Noise 40 – 55dB(A)@1m 45 – 60dB(A)@1m
Safety / Enclosure Safety EN 62040-1
EMC EN 62040-2 class C3
Certifications CE