back to all categoriesUPS THOR RM 10-30 kVA
The THOR RM is currently the most compact online double conversion UPS system and can be used in the smallest space. It is suitable for parallel redundant operation and can be extended to extremely long autonomy times using external battery packs.
With its rack design, it can be used as a plug-in device to set up an individually designed UPS system in all 19-inch network cabinets.
With an efficiency of over 95% in normal operation, it is one of the most effective and economical 3-phase UPS systems on the market and is therefore ideally suited to saving money.
Open in the catalogueDownloads
UPS THOR RM 10-30 kVA - Manual
1 file(s) 3.15 MB
UPS THOR RM 10-30 kVA - data sheet
1 file(s) 332.20 KB
Characteristics
- UPS classification VFI-SS-111 according to IEC 62040-3
- VFI sine wave output
- UPS software for all common OS
- Incl. RS232 / USB and expansion slot
- Integrated Emergency Power Off (EPO)
- Rack design: Can be used as a 19“ rack
- 24 months warranty
Special feature
- Excellent power factor of 1.0
- Parallel redundant operation of up to 4
systems possible - Cold start function (start in battery operation)
- Outstanding efficiency of over 95.5%
- Dry-In/Dry-Out interface as standard
- Multi colour display
Specifications
THOR RM | 10 kVA | 20 kVA | 30 kVA | |
---|---|---|---|---|
Power | Nominal power in VA/W | 10000/10000 | 20000/20000 | 30000/30000 |
Autonomy time 100/50% Load (cos. phi 0.8) | As standard in min. | 15/32 | 15/32 | 9/20 |
Quantity battery packs | 2 | 4 | 4 | |
Higher autonomy times | scalable with additional battery packs | |||
Technology | Online double conversion | VFI-SS-111 according to IEC 62040-3 | ||
Phase | Input / Output | 3-phase/ 3-phase | ||
Input | Nominal voltage configurable | 380/400/415VAC | ||
Input voltage range | 305~485Vac | |||
Input frequency range | 50/60 Hz (auto-detect) | |||
Distortion (THDi) | ≤3% @ linear load | |||
Output | Output voltage | 380/400/415VAC | ||
Voltage regulation | ±1% | |||
Power factor | 1.0 | |||
Frequency range | 1. Mains operation: synchronized with input when Input frequency >±10% (±1%/±2%/±4%/±5% optional) 2. Battery operation :50/60*(1±0.02%) Hz | |||
Transfer time | None | |||
Overload Capability (Line Mode) | ≤ 110% for 60 min, ≤ 125% for 10 min., ≤ 150% for 1 min. | |||
Voltage form | Sine wave | |||
Distortion (THD) | ≤2% @ linear load ≤4% @ non-linear load | |||
Efficiency | Normal mode | max. 95.5 % | ||
Battery | Type | Maintenance free lead-acid battery | ||
Life time | 5 years, optional 10 years | |||
Nominal DC-voltage | 480VDC, (optional 360 – 600VDC) | |||
Charging current | max. 18A (adjustable depending on the battery capacity) | |||
Recharging time | approx. 3 hours to 90% capacity depending on configuration | |||
Communication | Interface | RS232, USB, RS485, dry contacts, REPO, parallel and backfeed port | ||
Slot for further communication cards | for optional SNMP-card | |||
Display | LCD-Display and LEDs | |||
Dimensions / Weight | Dimensions UPS (HxWxD in mm) | 3HE x 481 x 808,5 | ||
Dimensions of battery extension (H x W x D in mm) | 3U x 481 x 750 | |||
Weight UPS in kg | 25 | 27 | ||
Weight battery pack in kg | 2×77 | 4×77 | ||
Protection | IP20 | |||
Terminals | Input | Fixed connection on terminals | ||
Output | Fixed connection on terminals | |||
Environmental conditions | Temperature | 0°C – 40°C, 20°C recommended | ||
Humidity | 0-90 % RH @ 0- 40°C (non-condensing) | |||
Acoustic Noise | < 55 dB (A)@1m | |||
Safety / Enclosure | Safety | EN 62040-1 | ||
EMC | EN 62040-2 Class C3 | |||
Certifications | CE |
Options for advanced communication and highest availability:
- SNMP / web card for monitoring in network environments
- Additional battery modules to increase the autonomy time to several hours
- Special designs available for industrial applications (connections / special housings, etc.)