back to all categories3-phase modular UPS THOR II TB20 10-60 kVA
Integrated Battery Modules
With the THOR II TB20, EFFEKTA® offers a compact, modular online double-conversion converter with 3-phase input and output in 3-level inverter technology.
Integrated, space-saving, modular battery expansion modules to increase the backup time, even retroactively.
The control elements, interfaces, battery packs and power modules are accessible from the front for easy commissioning, operation and maintenance.
Open in the catalogueDownloads
THOR II TB20 10-60 kVA – data sheet
1 file(s) 1.20 MB
THOR II TB20 10-60 kVA – Manual
1 file(s) 3.96 MB
Characteristics
- UPS classifi cation VFI-SS-111 according to IEC 62040-3
- VFI sine wave output can be switched to ECO High Effi ciency mode
- UPS software for all common OS
- Incl. RS232 / USB and expansion slot
- Integrated Emergency Power Off (EPO)
- 24 months warranty
Special feature
- Excellent power factor of 1.0
- Intelligent battery management with configurable charging mode
- N + X parallel redundant operation of up to 6 systems
- Redundant parallel control unit
- Power supply modules and fans redundant
- Outstanding efficiency of over 95.5% in normal operation, over 99% in eco mode
- Large 7 “multi-language touchscreen LCD panel
Specifications
THOR II T20 | 10-30 kVA/kW | 20-60 kVA/kW | |
---|---|---|---|
Power | Nominal power in kVA/kW | 10-30 kVA/kW | 20-60 kVA/kW |
Power per module | 10 kVA/kW | 20 kVA/kW | |
Number of modules max. | 3 | ||
Backup time | On request / depending on the battery configuration | ||
Technology | n + x technology scalable / VFI-SS-111 according to IEC 62040-3 | ||
Phases | Input / Output | 3-phase / 3-phase | |
Input | Configurable nominal voltage | 380 / 400 / 415 VAC | |
Input voltage range | 138 ~ 485 VAC | ||
Input frequency range | 40Hz – 70Hz | ||
Mains feedbacks | THDI | ≤3 % (100% nichtlineare Last) | |
Output | Output voltage | 380 / 400 / 415 VAC | |
Voltage regulation | ±1 % | ||
Frequency range Normal mode | ±1 % / ±2 % / ±4 % / ±5 % / ±10 % of the nominal frequency (optional) | ||
Frequency range Battery mode | 50/60 Hz ± 0,2 % | ||
Transfer time | None | ||
Overload | For mains operation: 105 % < load ≤ 110 %: Switching to bypass after 60 min. 110 % < load ≤ 125 %: Switchover to bypass after 10 min 125 % < load ≤ 150 %: Switchover to bypass after 1 min 125 % < load ≤ 150 %: Switchover to bypass after 1 min | ||
THD | > 150 %: immediate switch-off | ||
Voltage form | Sine wave | ||
Effi ciency | Normal-Mode | max. 95.5 % | |
Batteries | Type | Maintenance free lead-acid battery | |
Service life expectancy | 5 / 10 Jahre | ||
DC nominal voltage | ±240 VDC | ||
Batteries used | Max. 5 battery slots with max. 40 x 12V, 9.5 AH batteries per battery slot | ||
Maximum charging current | 18 A power module (charging current is set according to the battery bank equipment) | ||
per UPS cabinet | 54 A per UPS cabinet | ||
Time to recharge | depending on battery capacity | ||
Communication | Interfaces | CAN, RS232, RS485, LBS, parallel, relay card, SNMP card (optional) | |
Display | multilingual LC display | ||
Dimensions / weight | UPS dimensions (H x W x D in mm) | 2000 x 600 x 1000 | |
UPS modules (H x W x D in mm) | 86 (2U) x 440 x 620 | ||
Weight UPS in kg (without batt.) | approx. 363 kg | ||
UPS modules | 19 kg / 21 kg | ||
Weight battery bank (with batt.) | approx. 120 kg | ||
Protection class | IP20 | ||
Connections | Input | Output | fixed connection on terminals | fixed connection on terminals | |
Environmental conditions | Temperature | [0 – 40 °C], Recommended: + 15 °C…+ 25 °C | |
Humidity | 0 ~ 95 % (non-condensing) | ||
Operating noise | < 61 dB | ||
Protection / standards | Safety | EMC | Service | EN 62040-1 | EN 62040-2 | EN 62040-3 | |
Certification | CE |
Options for extended communication and highest availability:
- SNMP/web for monitoring in network environments
- Additional batteries to increase backup time to several hours
- External manual bypass