back to all categories3-phase modular UPS THOR II T50 50-600 kVA
With the THOR II T50, EFFEKTA® offers a modern online double conversion ups with 3-phase input & output in 3-level inverter technology, built with powerful 50 kW power modules.
All operating elements, interfaces and power modules are ac-cessible from the front for easy commissioning, operation and maintenance.
Intelligent battery management with configurable charging mode ensures long battery life. Furthermore, battery tests are individually configurable.
With an efficiency of over 96 % in normal operation, it is one of the most effective and economical UPS systems on the market and thus ideally suited for saving money.
Downloads
UPS THOR II T50_50-600 kVA - data sheet
1 file(s) 292.24 KB
UPS THOR II T50_50-600 kVA - Manual
1 file(s) 6.81 MB
Characteristics
- UPS classification VFI-SS-111 according to IEC 62040-3
- VFI sine wave output can be switched to ECO High Efficiency mode
- UPS software for all common OS
- Incl. RS232 / USB and expansion slot
- Integrated Emergency Power Off (EPO)
- 24 months warranty
Special feature
- Excellent power factor of 1.0
- Temperature sensor for temperature-controlled charging voltage to increase battery life
- Redundant parallel control unit
- Power supply modules and fans redundant
- Outstanding efficiency of 96 % in normal operation and 99 % in ECO mode
- Dry-In/Dry-Out interface as standard
Specifications
THOR II T50 | 150 kVA | 200 kVA | 300 kVA | 400 kVA | 500 kVA | 600 kVA | ||
---|---|---|---|---|---|---|---|---|
Power | Nominal power in kVA/kW | 50-150 | 50-200 | 50-300 | 50-400 | 50-500 | 50-600 | |
Power per modul | 50 kVA/kW | |||||||
Number of modules max. | 3 | 4 | 6 | 8 | 10 | 12 | ||
Backup time | on request / depending on the battery configuration | |||||||
Technology | Online double conversion | n + x technology scalable / VFI-SS-111 according to IEC 62040-3 | ||||||
Phases | Input / Output | 3-phase / 3-phase | ||||||
Input | Configurable nominal voltage | 380/400/415 VAC | ||||||
Input voltage range | 305~485 VAC | |||||||
Input frequency range | 40Hz-70Hz | |||||||
Circuit feedback | THDI | ≤3% (100% non-linear load) | ||||||
Output | Output voltage | 380/400/415 VAC | ||||||
Voltage regulation | ±1 % | |||||||
Frequency range | normal operation | ±1% / ±2% / ±4% / ±5% / ±10% der Nennfrequenz (optional) | ||||||
battery operation | (50/60 ±0,1) Hz | |||||||
Transfer time | none | |||||||
Overload inverter | 105% < load ≤ 110% for 60 min, 110% < load ≤ 125% for 10 min, 125% < load ≤ 150% for 1 min, then switching to bypass | |||||||
Voltage form | sinusoidal | |||||||
Efficiency | Normal-Mode / ECO-Mode | max. 96 % / 99 % | ||||||
Battery | Type | maintenance free lead-acid battery | ||||||
Service life expectancy | 10–12 Years | |||||||
DC nominal voltage | ±180V/192V/±204V/±216V/±228V/±240/±252/±264/±276/±288/±300VDC (30/32/34/36/38/40/42/44/46/48/50 blocks adjustable) | |||||||
Maximum charging current | 20 A per module (charging current is set according to the battery bank capacity) | |||||||
Time to recharge | depending on battery capacity | |||||||
Communication | Interfaces | CAN, RS232, RS485, LBS, Parallel, dry contacts, SNMP-card (optional) | ||||||
Display | multilingual 7”-LC-Display | |||||||
Dimensions / weight | UPS (HxWxD in mm) | 1200x600x 850 | 1600x600x 850 | 2000x600x 850 | 2000x1200x 850 | 2000x1400x 850 | ||
UPS w/o modules in kg | 180 | 200 | 260 | 450 | 480 | 550 | ||
Battery cabinet | depending on battery capacity | |||||||
UPS modules (HxWxD in mm) | 130 (3HE) x 440 x 620 | |||||||
UPS modul in kg | 34 | |||||||
Protection class | IP20 | |||||||
Connections | Input | fixed connection on terminals | ||||||
Output | fixed connection on terminals | |||||||
Environmental conditions | Temperature | [0 – 40 °C], Recommended: + 15 °C…+ 25°C | ||||||
Humidity | 0-95 % RH @ 0- 40°C (non-condensing) | |||||||
Operating noise | < 70 dB | |||||||
Protection / Standards | Safety | EMC | Service | IEC 62040-1 | IEC 62040-2 | IEC 62040-3 | ||||||
Approvals | CE |
Options for extended communication and highest availability:
- SNMP/web for monitoring in network environments
- Additional batteries to increase backup time to several hours
- External manual bypass for scheduled UPS maintenance or UPS replacement without shutdown