AC large UPS TRITON M2, 60-80 kVA
With the TRITON EFFEKTA® offers a modern, modular design, online double conversion UPS with 3-phase input & output.
The system is operated with two 30 or 40kVA power modules. Further up to 4 of these systems can be operated in parallel.
The power modules allow easy maintenance and replacement and therefore low service costs (very low MTTR value).
Datenblatt (PDF, 715.52 KB)
Zusätzliche Informationen
Downloads
Eigenschaften
- 24 months‘ warranty
- 3-step gentle battery charging method
- Easy maintenance through modular design
- EPO (remote shutdown)
- Extensive communication interfaces
- High efficiency (up to 95%)
- High input power factor up to 1 (0.99)
- High output power factor (0,9)
- Large input voltage range
- Management software for all common OS
- Online double conversion with sinusoidal output
- Switchable to ECO mode (> 98%, line-interactive)
- Temperature-controlled fan
- UPS classification VFI-SS-111 (IEC 62040-3)
Technische Details
TRITON M2 | 60 kVA | 80 kVA | |
---|---|---|---|
Power | Power in VA | 60000 | 80000 |
Power in W | 54000 | 72000 | |
Autonomy time 100% / 50% load (cos. phi 0.7) | With internal batteries in minutes | 7 / 17 | 4 / 10 |
Longer autonomy times on request | |||
Technology | Online double conversion | VFI-SS-111 in accordance with IEC 62040-3 | |
Phase | Input / Output | 3-phase / 3-phase | |
Input | Nominal voltage | 380/400/415 VAC | |
Input voltage range | 208-478 VAC | ||
Input frequency range | 50/60 Hz (Auto-Sensing) | ||
Circuit feedback THDI | < 3% | ||
Output | Output voltage | 380/400/415 VAC | |
Voltage Regulation | ±2% | ||
Power factor | 0.9 | ||
Frequency Range | 50 Hz or 60 Hz ± 1 Hz | ||
Transfer time | none | ||
Overload Capability (Line Mode) | < 125%: 10 min. / < 150%: 1 min. | ||
Voltage form | sine wave |
||
Efficiency | Normal mode / ECO mode | max. 95% / 98% | |
Battery | Type | Maintenance free lead-acid battery | |
Life time | 5 years, optional 10 years | ||
Charging current (max) | 10 A | ||
Recharging time | 8 h, dependent on accumulator capacity | ||
Communication | Interface | USB, RS232, RS485, EPO, REPO dry contact, Temp.sensor | |
Communication cards | Optional relay contacts or SNMP card | ||
Slot for communication cards | 2 | ||
Display | multi language LC-Display | ||
Parallel switching | Max. 4 systems for redundancy or to boost performance | ||
Dimensions / Weight | Dimensions UPS (H x W x D in mm) | 1200 x 600 x 780 | |
Weight UPS (without accumulators) | 189 kg | 195 kg | |
Dimensions of battery extension (H x W x D in mm) | 1200 x 600 x 780 | ||
Weight battery cabinet with standard configuration | 606 kg | 881 kg | |
Protection | IP 20 (optionally higher protection class possible) | ||
Terminals | Input | Fixed connection on terminals | |
Output | Fixed connection on terminals | ||
Environmental conditions | Temperature | 0°C – 40°C, 20°C recommended | |
Humidity | 0-90 % RH @ 0- 40°C (non condensing) | ||
Acoustic Noise | < 55 dB | ||
Safety / Enclosure | Safety | EN 62040-1 | |
EMC | EN 62040-2 class C3 | ||
Certifications | CE |