3-phase modular UPS THOR II T20 10-200 kVA
With the THOR II T20, EFFEKTA® offers a modular double conversion UPS with 3-phase input & output in 3-level inverter technology. Nearly all operating elements, interfaces and power
modules are accessible from the front for easy commissioning, operation and maintenance. Intelligent battery management with confi gurable charging mode ensures long battery life. Furthermore, battery tests are individually confi gurable. The current consumption is almost ideally sinusoidal. Furthermore, the THOR II offers a
power factor of 1.0. With an effi ciency of over 95.5% in normal operation, it is one of the most effective and economical UPS systems on the market and thus ideally suited for saving money.
Datenblatt (PDF, 332.43 KB)
Zusätzliche Informationen
Downloads
Besonderheiten
- Adjustable battery voltage (variable number of batteries)
- N+X parallel redundant operation of up to 4 systems possible
- Outstanding efficiency of 95.5% in normal operation and 99% in ECO mode
- Power supply modules and fans redundant
- Redundant parallel control unit
- Simple service through modular structure
- Temperature sensor for temperature-controlled charging voltage to increase battery life
Eigenschaften
- Dry-In/Dry-Out interface as standard
- Excellent power factor of 1.0
- Incl. RS232 / USB and expansion slot
- Integrated Emergency Power Off (EPO)
- UPS classification VFI-SS-111 according to IEC 62040-3
- UPS software for all common OS
- VFI sine wave output can be switched to ECO High Efficiency mode
Technische Details
THOR II T20 | T20-60 | T20-100 | T20-200 | |
---|---|---|---|---|
Power | Nominal power in kVA/kW | 10-60 | 10-100 | 10-200 |
Power per module | 10 or 20 kVA/kW | |||
Number of modules max. | 3 | 5 | 10 | |
Backup time | On request / depending on the battery configuration | |||
Technology | n+x technology scalable / VFI-SS-111 according to IEC 62040-3 | |||
Phases | Input / Output | 3-phase / 3-phase | ||
Input | Configurable nominal voltage | 380/400/415 VAC | ||
Input voltage range | 138 ~ 485 VAC | |||
Input frequency range | 40 Hz - 70 Hz | |||
Mains feedbacks | THDI | ≤3 % (100% nonlinear load) | ||
Output | Output voltage | 380/400/415 VAC | ||
Voltage regulation | ±1 % | |||
Frequency range normal operation | ±1 % / ±2 % / ±4 % / ±5 % / ±10 % of the nominal frequency (optional) | |||
Frequency range battery operated | 50/60 Hz ± 0,2 % | |||
Transfer time | none | |||
Overload | For mains operation: 105% < load ≤ 110%: Switching to bypass after 60 min. 110 % < load ≤ 125 %: Switchover to bypass after 10 min 125 % < load ≤ 150 %: Switchover to bypass after 1 min > 150 %: immediate switch-off110 % < Last ≤ 125 %: Umschaltung in den Bypass nach 10 min 125 % < Last ≤ 150%: Umschaltung in den Bypass nach 1 min > 150 %: sofort Abschaltung |
|||
Voltage form | Sine wave | |||
Efficiency | Normal-Mode / ECO-Mode | 95,5 in line mode / 99 % in ECO mode | ||
Batteries | Type | Maintenance free lead-acid battery | ||
Service life expectancy | 5 / 10 years | |||
DC nominal voltage | ±180 V/192 V/±204 V/±216 V/±228 V/±240/±252/±264/±276/±288/±300 VDC (30/32/34/36/38/40/42/44/46/48/50 blocks adjustable)(30/32/34/36/38/40/42/44/46/48/50 Blöcke einstellbar) |
|||
Maximum charging current | 18 A per module (charging current is set according to the battery bank capacity) | |||
Time to recharge | from 5 hours, depending on battery capacity | |||
Communication | Interfaces | CAN, RS232, RS485, LBS, parallel, relay card, SNMP card (optional) | ||
Display | multilingual LC display | |||
Dimensions / weight | UPS (HxWxD in mm) | 1200 x 600 x 850 | 1400 x 600 x 850 | 2000 x 600 x 500 |
UPS w/o power modules in kg | app. 139 | app. 187 | app. 221 | |
Battery cabinet (HxWxD in mm) | 1200 x 600 x 780 or 2000 x 600 x 850 (depending on configuration) | |||
Battery cabinet (empty weight) | 125 / 217 kg | |||
UPS modules (H x W x D in mm) | 86 (2U) x 440 x 620 | |||
Weight UPS modules | 21 kg | |||
Protection class | IP20 | |||
Connections | Input | Output | fixed connection on terminals | fixed connection on terminals | ||
Environmental conditions | Temperature | [0 - 40 °C], Recommended: + 15 °C…+ 25°C | ||
Humidity | 0~- 95 % (non-condensing) | |||
Operating noise | < 58 dB | < 61 dB | < 68 dB | |
Protection/standards | Safety | EMC | Service | EN 62040-1 | EN 62040-2 | EN 62040-3 | ||
Approvals | CE |