UPS Modular Tower THOR 31: Flexible 6-30 kVA solutions for industrial power supply
For the highest demands on flexibility and reliability, EFFEKTA® the new UPS system THOR 31 with 3-phase input and 1-phase output. The outstanding efficiency of up to 98% in ECO mode makes this system one of the most efficient UPS systems on the market. The modular design with 6 kVA / kW modules allows a highly available UPS system up to 30 kW to be set up with a total of 5 modules. With their help, n+x redundancy can be set up. In addition, up to 4 systems can be connected in parallel.
data sheet (PDF, 172.14 KB)
Features
- Automatic battery test adjustable via display
- Dry-In/Dry-Out interface as standard
- Low noise thanks to intelligent fan control
- Excellent power factor of 1,0
- Multilingual 7" color LCD touch display
- Network perturbations THDi <3 %
- Parallel redundant n+x operation possible
- Outstanding efficiency of up to 94% in normal operation
- Unbeatable price advantage in this performance class
Features
- 24 months warranty
- UPS classification VFI-SS-111 according to IEC 62040-3
- Extremely compact design
- remaining battery time indicator on LCD display
- Incl. 2 expansion slots
- Integrated remote emergency stop contact (REPO)
- Online double converter with sine output switchable to high efficiency mode
- Service-friendly battery replacement
- UPS software for all common operating systems
Technical details
| model THOR Modular 31 | 6 – 30 kVA | |
|---|---|---|
| Offering | Rated power in VA/W | 6000 - 30000 |
| power per module | 6kVA / 6kW | |
| bridging time | UPS system THOR Modular 31 | Configurable depending on number of modules and battery capacity |
| Technology | online double converter | n+x technology scalable / VFI-SS-111 according to IEC 62040-3 |
| phases | Input Output | 1-phase/1-phase or 3-phase/1-phase |
| Input | Nominal voltage configurable | 380/400/415VAC or 220/230/240VAC |
| Input voltage range | 208~478 VAC or 120~276 VAC | |
| input frequency range | 40-70 Hz (automatic detection) | |
| grid perturbations THDi | ≤3% (100% non-linear load) | |
| Output | output voltage | 220/230/240 VAC |
| power factor | 1,0 | |
| Voltage regulation | ±1 % | |
| frequency range | Mains operation: ±1%, ±2%, ±4%, ±5%, ±10% of nominal frequency (Optional) Battery operation: 50 Hz / 60 Hz ± 0,2 Hz |
|
| switching time | 0 ms | |
| Overload Normal Operation | ≤110%: for 60 min., ≤125%: for 10 min., ≤150%: for 1 min., ≥150% immediate transfer to bypass |
|
| overload battery operation | ≤110%: for 10 min., ≤125%: for 1 min., ≤150%: for 1 sec., ≥150% immediate shutdown of the UPS |
|
| voltage form | Sine | |
| crest factor | 3:1 | |
| THD | ≤2% with linear load ≤5 % with non-linear load |
|
| Efficiency | normal operation | max. 94% |
| ECO mode | max. 98% | |
| Battery | Type | maintenance-free lead-acid batteries |
| service life expectancy | 5 years (optional 10 years) | |
| DC nominal voltage | 192-240 VDC adjustable, standard 240VDC | |
| Maximum charging current | max. 12A per power module / max. 60 A UPS system | |
| Communication | interface | RS232, 2xRS485, switching contacts, REPO |
| Expansion slot | 2 x for relay or SNMP card | |
| Display | LCD display and LED indicators | |
| Dimensions / weight | UPS dimensions (HxWxD in mm) | 1400 x 600 x 840 |
| Weight of UPS without modules in kg | 150 | |
| Weight of UPS power module in kg | 25 | |
| Dimensions of battery cabinet (HxWxD in mm) | 1200 x 600 x 780 | |
| Weight of battery cabinet in kg | depending on the battery configuration | |
| Protection class | IP20K | |
| Connections | Input | fixed connection on terminals |
| Output | fixed connection on terminals | |
| Environmental conditions | Temperature | 0°C – 40°C, 20°C recommended |
| humidity | 0-95% RH (non-condensing) | |
| protection / standards | Safety | EN 62040-1 |
| EMC | EN 62040-2 Class C3 | |
| approvals | CE | |
Matching this