Air-cooled all-in-one battery system OPTIM US A329-BAT
The OPTIM US A329-BAT is an air-cooled, high-voltage battery storage system based on lithium iron phosphate batteries. This system is particularly suitable for industrial and commercial applications, such as peak shaving and valley filling, increasing power capacity, storage systems for photovoltaic installations, and emergency power supplies. Designed for outdoor use, the battery storage system connects the power grid to the storage battery via a hybrid inverter, enabling bidirectional energy transfer between the DC battery of the storage system and the AC grid.
data sheet (PDF, 620.99 KB)
Additional Information
Downloads
Product Features
- Flexible configuration.
- Maximum safety.
- Long-term backup.
- Easy setup and maintenance.
Technical details
| General data | M5-300kWh-1500V |
|---|---|
| Dimensions (W*D*H mm, without inverter) | 1500 * 1300 * 2200 |
| Weight (tons) | 3,5 |
| Operating temperature range (°C) | -40~55* |
| IP protection class | IP 55 |
| Altitude (m) | ≤4000 |
| humidity | 0 ~ 95% |
| Firefighting | Aerosol |
| Cooling system | air cooling |
| Cooling system power consumption (kW, cooling/heating) | 5/3,7 |
| Auxiliary power consumption (kW, continuous/peak, incl. HVAC) | 2,35/4.26 |
| Maximum number of parallel | 5 |
| Corrosion Protection | C3 (C5 optional) |
| Certification | UN38.3/UN 3480/IEC62619/IEC62040-1/CE/UKCA (EMC/RED)/VDE2510-50/UL1973/UL9540A |
| Battery data | M5-300kWh-1500V |
|---|---|
| battery type | Li-ion (LFP) |
| Nominal capacity (kWh) | 329 |
| Continuous C-rate | 0,5C |
| Max. operating current (A) | 180 |
| depth of discharge | 98% (single strand) |
| Cycle life | > 7000 |
| DC voltage range (VDC) | 1176-1491 (single strand) |
| Rated operating current (A) | 122,5 |
| Overall efficiency at 0,5 C-rate | 96 % |
| operation mode | M5-300kWh-1500V |
|---|---|
| Communication type | RS485 (MODBUS RTU)/LAN (MODBUS TCP/IP)/CAN |
| Operational logic | Peak shaving/load shifting/self-consumption/backup |
| *Degradation occurs at temperatures below 10°C or above 40°C. | |