Air-cooled all-in-one battery system OPTIM US A100-OMNI 108~648kWh 100~600kW

Air-cooled all-in-one battery system OPTIM US A100-OMNI

The OPTIM US A100-OMNI is an air-cooled, high-voltage battery storage system based on lithium iron phosphate batteries. This system is particularly suitable for industrial and commercial applications, such as peak shaving and valley filling, increasing power capacity, storage systems for photovoltaic installations, and emergency power supplies. Designed for outdoor use, the battery storage system connects the power grid to the storage battery via a hybrid inverter, enabling bidirectional energy transfer between the DC battery of the storage system and the AC grid.
data sheet (PDF, 646.94 KB)

Technical details


General dataM1C-100kW/108kWh
Dimensions (W*D*H mm, without inverter)1300 * 2485 * 1150
Weight (tons)2 (including battery)
Operating temperature range (°C)-25~45*
IP protection classIP55K
Sea level≤2000
humidity0 ~ 95%
FirefightingAerosol
Cooling systemair cooling
Cooling system power consumption (kW, cooling/heating)3 / 2
Auxiliary power consumption (kW, continuous/peak, incl. HVAC)2,5/4
Maximum number of parallel5
Corrosion ProtectionC5 (C4H air conditioning)
CertificationUN38.3/UN3481/IEC62619/IEC62040-1/CE/UKCA(EMC/RED)/
VDE2510-50/UL1973/UL9540A/UL9540
CE EMC/CE LVD/EN 50549-1: 2019/EN 50549-2: 2019/IEC 61000-6-2/IEC 62477-1
Battery dataM1C-100kW/108kWh
battery typeLi-ion (LFP)
Nominal capacity (kWh)108
Max. / continuous C-rate1C
depth of discharge98% (single strand)
Cycle life> 7000
DC voltage range (VDC)667-828 (single strand)
Max. / Continuous operating current (A)148
Overall efficiency at 0,5 C-rate95 %
PCS DC/AC data in mains operationM1C-100kW/108kWh
AC rated power (kW)100
AC nominal output voltage (Vac)230/400
AC nominal output frequency (Hz)50
Maximum AC current (A)145 (Linear Load)
Overload capacity120%@60sec
AC power factor1,0 (leading) ~ 1,0 (lagging)
CEC efficiency97,3% (peak 98,1%)
Insulation typeno isolation
operation modeM1C-100kW/108kWh
Communication typeModbus TCP/IP, Modbus RTU
Operational logicTemperature range/ancillary services/arbitrage in electricity trading/load control/backup
*Degradation occurs at temperatures below 10°C or above 40°C.