Air-cooled all-in-one battery system OPTIM US A100-HY 52~520kWh 25~500kW

Air-cooled all-in-one battery system OPTIM US A100-HY

The OPTIM US A100-HY is an air-cooled, high-voltage battery storage system based on lithium iron phosphate batteries. This system is particularly suitable for industrial and commercial applications, such as peak shaving and valley filling, increasing power capacity, storage systems for photovoltaic installations, and emergency power supplies. Designed for outdoor use, the battery storage system connects the power grid to the storage battery via a hybrid inverter, enabling bidirectional energy transfer between the DC battery of the storage system and the AC grid.
data sheet (PDF, 612.16 KB)

Product Features

  • Integrated hybrid inverter.
  • Maximum safety.
  • Flexible configuration.
  • Easy setup and maintenance.
  • Load peak capping

Technical details


General dataM1C 100kW/104kWh
Dimensions (W*D*H mm, without inverter)1500 * 1125 * 2195
Weight (tons)1,9 (including battery)
Operating temperature range (°C)-20-50*
IP protection classIP55K
Sea level≤2000
humidity0 ~ 95%
FirefightingAerosol
Cooling systemair cooling
Cooling system power consumption (kW, cooling/heating)2/1
Auxiliary power consumption (kW, continuous/peak, incl. HVAC)1,5/3
Maximum number of parallel5
Corrosion ProtectionC3 (C5 optional)
CertificationUN38.3/UN3481/IEC62619/IEC62040-1/CE/UKCA(EMC/RED)/VDE2510-50/UL1973/UL9540A/UL9540
G99/VDE-AR-N 4105/EN 50549-1/EN 50549-10/EIFS 2018.2/IEC 62116/IEC 61727/
IEC 60068/IEC 61683/EN 50530
Battery dataM1C 100kW/104kWh
battery typeLi-ion (LFP)
Nominal capacity (kWh)104
Max. / continuous C-rate1/0,5
depth of discharge98% (single strand)
Cycle life> 7000
DC voltage range (VDC)594-792 (single strand)
Max. / Continuous operating current (A)148/74
Overall efficiency at 0,5 C-rate95 %
Hybrid data in network operationM1C 100kW/104kWh
AC rated power (kW)50/100
AC nominal output voltage (Vac)400
AC nominal output frequency (Hz)50/60
Maximum AC current (A)76 (Linear Load)
Overload capacity110 %
AC power factor>0,99 (0,8 leading ~ 0,8 lagging)
CEC efficiency97,4% (max. 97,8%)
Insulation typeno isolation
Response time (mains operation to island operation)<10ms
operation modeM1C 100kW/104kWh
Communication typeModbus TCP/IP, Modbus RTU
Operational logicPeak load shaving/load shifting/self-consumption/backup
*Degradation occurs at temperatures below 10°C or above 40°C.