TRITON M2: Powerful UPS solutions for large systems (60-80 kVA)
With the TRITON, EFFEKTA® offers a modern, modular online double-converter with 3-phase input and output. The system is operated with 2 power modules of 30 or 40 kVA each. Furthermore, up to 4 of these systems can be operated in parallel. The power modules enable easy maintenance and replacement and thus low service effort (very low MTTR value).
data sheet (PDF, 707.64 KB)
Features
- 24 months warranty
- 3-stage gentle battery charging process
- Easy service thanks to modular design
- EPO (emergency stop / remote shutdown)
- Large voltage input window
- Excellent output power factor of 0,9
- High input power factor up to 1 (0,99)
- High efficiency (up to 95%)
- management software for all common OS
- Online double-wave converter with sine output THDI ≤ 3%
- Temperature-controlled fans
- Extensive communication interfaces
- Switchable to ECO mode (> 98%, line-interactive)
- UPS classification VFI-SS-111 according to IEC 62040-3
Technical details
| TRITON M2 | 60 kVA | 80 kVA | |
|---|---|---|---|
| Offering | Rated power in VA | 60000 | 80000 |
| Rated power in W | 54000 | 72000 | |
| bridging time 100% / 50% load (cos. phi 0,7) | Standard equipment in min. | 7 / 17 | 4 / 10 |
| longer autonomy times on request | |||
| Technology | online double converter | VFI-SS-111 according to IEC 62040-3 | |
| phases | input / output | 3-phase / 3-phase | |
| Input | Nominal voltage configurable | 380/400/415 VAC | |
| Input voltage range | 208-478 VAC | ||
| input frequency range | 50/60 Hz (automatic detection) | ||
| grid perturbations THDI | <3% | ||
| Output | output voltage | 380/400/415 VAC | |
| Voltage regulation | ± 2% | ||
| power factor | 0,9 | ||
| frequency range | 50 Hz or 60 Hz ± 1 Hz | ||
| switching time | no | ||
| Overload Normal Operation | < 125% for 10 minutes / < 150% for 1 minute | ||
| voltage form | Sine | ||
| Efficiency | Normal mode / ECO mode | max. 95% / 98% | |
| Battery | Type | maintenance-free lead-acid batteries | |
| service life expectancy | 5 years, optionally 10 years | ||
| Maximum charging current | 10 A | ||
| time to recharge | from 8 hours, depending on battery capacity | ||
| Communication | interface | USB, RS232, RS485, EPO, REPO dry contact, Temp.sensor | |
| communication cards (option) | Optional relay or SNMP card | ||
| slots for communication cards | 2 | ||
| Display | multilingual LCD display | ||
| parallel circuit | max. 4 systems for redundancy or to increase performance | ||
| Dimensions / Weight | UPS dimensions (HxWxD in mm) | 1200 x 600 x 780 | |
| Weight UPS in kg (with standard battery) | 189 | 195 | |
| Dimensions of battery extension (HxWxD in mm) | 1200 x 600 x 780 | ||
| Weight of battery cabinet with standard equipment in kg | 606 | 881 | |
| Protection class | IP 20 (higher protection classes available optionally) | ||
| Connections | Input | fixed connection on terminals | |
| Output | fixed connection on terminals | ||
| Environmental conditions | Temperature | 0°C – 40°C, 20°C recommended | |
| humidity | 0-90 % RH @ 0- 40°C (non-condensing) | ||
| Operating noise | <55 dB | ||
| protection / standards | Safety | EN 62040-1 | |
| EMC | EN 62040-2 Class C3 | ||
| approvals | CE | ||
Matching this