Controller Orion

Controller Orion: Intelligent control for UPS battery management

The Orion System Controller is the latest version of the central control unit for the EFFEKTA® DC power supply systems. The user-friendly display provides the most important information about the status of the power supply system. New functions such as the "efficiency mode" help to reduce the operating costs of the systems. Modules that are not required, e.g. when the load is lower, are shut down to increase the efficiency of the system. An integrated web server offers a user-friendly interface with a standard browser for both local and remote communication.
data sheet (PDF, 666.47 KB)

Features

  • 24 months warranty
  • Sophisticated battery management
  • Exchange possible during ongoing operation of the system
  • Digital System Bus
  • Easy system expansion
  • Energy saving features
  • Remote monitoring via modem or LAN
  • Freely programmable relay contacts
  • Advanced plant control/monitoring
  • Integrated WEB Server
  • Pluggable
  • monitoring of additional devices

Technical details


Orion
InputInput voltage range18 - 75 VDC
Input current0,75 ADC max.
entrance protection2A fuse, external
Benutzerschnittstellestatus indicatorLED «ok», LED «alarm»
Featuresrectifier interfaceDigital, CAN-based
number of rectifiersUntil 128
digital inputsUntil 225
Relay outputsUntil 97
temperature measurementsUntil 96
voltage, currentUntil 96
local / remote monitoringLAN/RS232/WEB browser
remote alarmrelay contacts / SNMP
SNMP managementStandard SNMP Manager
FeaturesTemperature-compensated floating charge voltage
battery center point measurement
battery block voltage (up to 256)
battery charging current limitation
fast charging, equalizing charging
battery test (optionally with capacity measurement)
Partial load and battery shutdown (up to 96)
Battery - deep discharge protection, mains fault detection
Individual rectifier control
Energy saving mode, cyclic rectifier mode
Sequential rectifier start
PLC functionality
event generator, 200 log entries
Environmental conditionsTemperature-35… + 60 ° C
humidity0-90 % RH @ 0- 40°C (non-condensing)
Safety and StandardsEN 60950 Class I, UL 60950, CAN / CSA - C22.2
EN 55022, Class B
IN 300 386-2
Coolingconvection
Installation directionAll
Protection classIP 20