ADIRA T 6-10 kVA UPS in tower design – Ideal power supply for medium-sized companies
The ADIRA T is currently the most compact double-conversion UPS system and can be used in the smallest of spaces. Its autonomy time can be extended extremely flexibly using external battery packs. The power consumption is almost ideally sinusoidal. The ADIRA T also offers a power factor of 1,0. With an efficiency of up to 95% in normal operation, it is one of the most effective and economical UPS systems on the market and is therefore ideal for saving money.
data sheet (PDF, 763.51 KB)
Features
- Number of batteries per string adjustable from 16-20 pcs.
- Dry-In/Dry-Out interface as standard
- Low noise thanks to intelligent fan control
- Larger 12 A charger for higher charging currents (XL version)
- Excellent power factor of 1,0
- Multilingual LCD display
- Parallel redundant operation possible
- Outstanding efficiency of up to 95% in normal operation / 98% in ECO mode
Features
- 24 months warranty
- UPS classification VFI-SS-111 according to IEC 62040-3
- Extremely compact design
- remaining battery time indicator on LCD display
- Incl. RS232/USB and expansion slot
- Integrated emergency stop switch (EPO)
- Online double converter with sine output switchable to high efficiency mode
- UPS software for all common OS
Technical details
| ADIRA-T | ADIRA-T 6000 | ADIRA-T 10000 | |
|---|---|---|---|
| Offering | performance in VA | 6000 | 10000 |
| Power in W | 6000 | 10000 | |
| bridging time 100% / 50% load (cos. phi 0,7) | Standard equipment in min. | 12 / 25 | 6 / 13 |
| longer autonomy times | with XL variant on request | ||
| Technology | online double converter | VFI-SS-111 according to IEC 62040-3 | |
| phases | input / output | 1-phase / 1-phase | |
| Input | Nominal voltage configurable | 220/230/240 VAC | |
| Input voltage range | 160-276 VAC | ||
| input frequency range | 50/60 Hz (automatic detection) | ||
| Output | output voltage | 220/230/240 VAC | |
| Voltage regulation | ± 1% | ||
| frequency range | 50 Hz or 60 Hz ± 1 Hz | ||
| switching time | no | ||
| Overload Normal Operation | < 125% for 10 min., < 150% for 30 sec. | ||
| voltage form | Sine | ||
| Efficiency | normal operation | Max. 95% | |
| ECO mode | max 98% | ||
| Battery | Type | maintenance-free lead-acid batteries | |
| service life expectancy | 5 years, optionally 10 years | ||
| DC nominal voltage | 240 VDC | ||
| Maximum charging current | 4 A standard / 12 A XL version | ||
| time to recharge | approx. 3 hours to 90% capacity depending on the equipment | ||
| Communication | interface | RS232, USB, switch contacts, EPO, parallel port | |
| Expansion slot | Optional relay or SNMP card | ||
| Display | LCD display and LED indicators | ||
| Dimensions / Weight | UPS dimensions (HxWxD in mm) | 353 x 225 x 600 | |
| Dimensions battery extension (HxWxD in mm) optional | 589 x 225 x 490 | ||
| Weight UPS without batteries (XL) in kg | 14 | 16 | |
| Weight including internal batteries in kg | 68 | 70 | |
| weight of the battery bank | 66 kg / kg 116 | ||
| Protection class | IP 20 | ||
| Connections | Input | fixed connection on terminals | |
| Output | fixed connection on terminals | ||
| Environmental conditions | Temperature | 0°C – 40°C, 20°C recommended | |
| humidity | 0-90 % RH @ 0- 40°C (non-condensing) | ||
| Operating noise | 40 - 55 dB (A)@1m | 45 - 60 dB (A)@1m | |
| protection / standards | Safety | EN 62040-1 | |
| EMC | EN 62040-2 Class C3 | ||
| approvals | CE | ||