Line-Interactive Office-RM: UPS systems for the office area
The OFFICE RM is a cost-effective line-interactive system that protects sensitive consumers from power outages. It is available in 600 and 1000 VA power levels. This device can be used in particular for computers and small servers or for active network components in 19" system cabinets. With its extremely compact design and low installation depth, the OFFICE RM is particularly suitable for smaller network cabinets.
data sheet (PDF, 874.43 KB)
Features
- Silent (without fan)
- Automatic voltage regulation AVR with boost & buck function
- User-friendly illuminated LCD display
- Low installation depth: 600 VA model only 230 mm 1000 VA model only 300 mm
- Compact design
Features
- 24 months warranty
- Automatic frequency detection
- Microprocessor control
- UPS classification VI-SY-333 according to IEC 62040-3
- Incl. slot for SNMP adapter
- Incl. USB interface
- UPS software for the common OS
Technical details
| OFFICE RM | OFFICE RM 600 | OFFICE RM 1000 | |
|---|---|---|---|
| Performance | Rated power in VA | 600 VA | 1000 VA |
| Rated power in W | 360 W | 600 W | |
| bridging time | At PC load in min | 12 | 25 |
| Technology | Line-Interactive | VI-SY-333 according to IEC 62040-3 | |
| phases | input / output | 1-phase / 1-phase | |
| Input | nominal voltage | 220/230/240 VAC | |
| Input voltage range | 162-290 VAC | ||
| input frequency range | 60/50 Hz (automatic detection) | ||
| Output | Output voltage nom. | 220/230/240 VAC | |
| Voltage regulation | ± 10% | ||
| frequency range (battery operation) | 50 Hz or 60 Hz ± 1 Hz | ||
| switching time | 2-6 ms typical | ||
| Overload Normal Operation | < 125% for 10 min / < 150% for 30 sec | ||
| voltage form | Modified sine wave | ||
| Battery | Type | maintenance-free lead-acid batteries | |
| service life expectancy | 5 years (optional 10 years) | ||
| time to recharge | approx. 4-6 hours at 90% capacity | ||
| Communication | interface | USB, SNMP slot | |
| Display | LCD | ||
| Dimensions / Weight | UPS dimensions (HxWxD in mm) | 86 x 438 x 230 | 86 x 438 x 300 |
| Weight UPS in kg | 6,5 | 11,6 | |
| Protection class | IP 20 | ||
| Connections | Input | IEC (10A) | |
| Output | 8 x IEC C13 (10A) | ||
| Environmental conditions | Temperature | 0°C – 40°C, 20°C recommended | |
| humidity | 20-90% (non-condensing) | ||
| Operating noise | <40 dB (1 m) | ||
| protection / standards | Safety | IEC/EN62040-1, IEC/EN60950-1 | |
| EMC | IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8 | ||
| approvals | CE | ||
Matching this