Line-Interactive MTX series: Compact UPS systems for small to medium applications
The MTX is a modern line-interactive UPS with a power factor of 0,9. It is available in 800, 1100, 1500, 2000 and 3000 VA outputs. All important UPS information is easy to read on the clear, illuminated LC display. Its low noise level and simple design means it fits into any office environment. For longer backup times, the MTX UPSs can be extended with optionally available external battery packs.
data sheet (PDF, 1.35 MB)
Features
- All models can be expanded with external battery packs
- User-friendly illuminated LCD display
- early error detection
- Low noise (suitable for office environments)
- Green Mode: UPS switches off in battery mode if no load is detected
- Excellent power factor of 0,9
- Intelligent battery test with display
- Programmable UPS outputs
- RS-232 and USB interface as standard
- Silent ECO mode: Turns off the fan(s) when the batteries are full
Features
- 36 months warranty
- Automatic self-tests & frequency detection
- Auto restart when power returns
- High efficiency (up to 97%)
- Hot-swap
- cold start (start in battery mode)
- line-interactive technology
- management software
- sine wave output
- Slot for optional adapters: relay or SNMP card
- UPS classification VI-SS-311 according to IEC 62040-3
Technical details
| MTX | 800 | 1100 | 1500 | 2000 | 3000 | |
|---|---|---|---|---|---|---|
| Performance | Rated power in VA | 800 | 1100 | 1500 | 2000 | 3000 |
| Rated power in W | 720 | 990 | 1350 | 1800 | 2700 | |
| bridging time 100% / 50% load (cos. phi 0,7) | Standard equipment in min. | 7 / 17 | 5 / 12 | 7 / 17 | 5 / 12 | 6 / 14 |
| Standard equipment + battery bank (1 string) | 19 / 45 | 13 / 31 | 25 / 60 | 19 / 45 | 20 / 48 | |
| longer autonomy times on request | ||||||
| Technology | Line-Interactive | VI-SS-311 according to IEC 62040-3 | ||||
| phases | input / output | 1-phase / 1-phase | ||||
| Input | Nominal voltage configurable | 208/220/230/240 VAC | ||||
| Input voltage range | 170-280 VAC | |||||
| input frequency range | 50/60 Hz (automatic detection) | |||||
| Output | Output voltage nom. | 208/220/230/240 VAC | ||||
| Voltage regulation | ± 1,5% | |||||
| frequency range | 50 Hz or 60 Hz ± 1 Hz | |||||
| switching time | 2-6 ms typical / 10 ms max. | |||||
| Overload Normal Operation | < 120% 5 minutes | |||||
| overload battery operation | < 110% 1 minute | |||||
| voltage form | Sine | |||||
| Efficiency | normal operation | max 97% | ||||
| Battery | Type | maintenance-free lead-acid batteries | ||||
| service life expectancy | approx. 5 years, optionally 10 years | |||||
| Maximum charging current | 1,5 A | #colspan# |
||||
| Hot swappable | ja | |||||
| time to recharge | approx. 6 hours at 90% capacity | |||||
| Communication | interface | RS232, USB, EPO | ||||
| slot for additional communication card | Optional relay or SNMP card | |||||
| Display | Multilingual LCD display | |||||
| Dimensions / Weight | UPS dimensions (HxWxD in mm) | 240 x 145 x 376 | 240 x 145 x 484 | 338 x 190 x 427 | ||
| Dimensions battery bank (HxWxD in mm) optional | 240 x 145 x 397 | 338 x 190 x 416 | ||||
| Weight UPS in kg | depending on the equipment | |||||
| Protection class | IP 20 (higher protection classes available optionally) | |||||
| Connections | Input | IEC (10 A) | IEC (16 A) | |||
| Output programmable in segments | 8 x IEC C13 (10 A) | 8xIEC C13 10A | ||||
| 1xIEC C19 16A | ||||||
| Environmental conditions | Temperature | 0°C – 40°C, 20°C recommended | ||||
| humidity | 0-90 % RH @ 0- 40°C (non-condensing) | |||||
| Operating noise | Normal operation almost silent <45 dB | |||||
| protection / standards | Safety | EN 62040-1 | ||||
| EMC | EN 62040-2 Class C2 | |||||
| approvals | CE | |||||
Matching this